The user on the Primary computer where the project is started should have full control over this directory. Create a share name for the directory that does not contain any spaces.Create the directory at the determined location.WARNING: Do not choose a location that within the directory tree of another CIMPLICITY HMI project. The path name for the location cannot contain any spaces and the fully qualified path name should be 27 characters or less. Determine the location for the CIMPLICITY run-time project configuration data.Start->Programs->CIMPLICITY HMI->HMI->CIMPLICITY Options On the Secondary computer, stop all projects running using the CIMPLICITY Options utility.?Configure the directory for the CIMPLICITY HMI run-time project configuration on the secondary computer with the correct permissions. From the DOS command prompt on the Primary computer, execute a ping by hostname from the Secondary to the Primary computer, verifying that the TCP/IP address returned by ping command is the expected address for the primary computer.If this fails please see the Appendix B: Name Resolution and configure the cimhosts.txt file on the Primary computer. From the DOS command prompt on the Primary computer, execute a ping by hostname from the Primary to the Secondary computer, verifying that the TCP/IP address returned by the ping command is the expected for the secondary computer.Execute a ping by TCP/IP address from the Secondary to the Primary computer.Open up a DOS command prompt on the Secondary computer.Execute a ping command by TCP/IP address from the Primary to the Secondary computer.Open up a DOS command prompt on the Primary computer.